ZOU Zhe-qiang, ZHANG Xin-chao, MAO Xin-zhan, et al. Testing and analysis of MTBF of main equipments of coal mine monitoring system[J]. Industry and Mine Automation, 2013, 39(7): 1-4.
Citation: ZOU Zhe-qiang, ZHANG Xin-chao, MAO Xin-zhan, et al. Testing and analysis of MTBF of main equipments of coal mine monitoring system[J]. Industry and Mine Automation, 2013, 39(7): 1-4.

Testing and analysis of MTBF of main equipments of coal mine monitoring system

  • Publish Date: 2013-07-10
  • The paper introduced testing method of mean time between failures, did site test of mean time between failures in four coal mines to the same coal mine monitoring system, and got mean time between failures of main equipments of the monitoring system. It concluded: the values of mean time between failures of intrinsic safety power, gas sensor, CO sensor and wind speed sensor are relatively small, and these equipments should be the focus of future design and improvement; the monitoring system can achieve the index suggested in AQ 6201—2006 that mean time between failures should be not less than 800 hours; statistical results show that line fault of underground coal mine occurs frequently.

     

  • loading
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (63) PDF downloads(6) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return