TIAN Shu, ZHANG Sheng-chao. Research of Selcctive Distance Protection of Traveling Wave for Underground High-voltage Power Network[J]. Journal of Mine Automation, 2008, 34(3): 19-23.
Citation: TIAN Shu, ZHANG Sheng-chao. Research of Selcctive Distance Protection of Traveling Wave for Underground High-voltage Power Network[J]. Journal of Mine Automation, 2008, 34(3): 19-23.

Research of Selcctive Distance Protection of Traveling Wave for Underground High-voltage Power Network

More Information
  • The breaker often took place unselective overstep tripping when short circuit fault occurred in mine high-voltage power network, which is a technical problems and potential safety hazard of underground power supply existed for a long time. The paper used the correspondent relation between modulus maximum of wavelet transform and traveling wave singularity point to measure time of arriving protection installation of traveling wave, then calculated traveling wave speed under particular frequency of the cable in real time for accurate fault location. It made use of action time of protection increasing with fault distance to construct a fast and selective longitudinal protection system by microcomputer’s logic judgment, which is not influenced by protections’ interlock.
  • Related Articles

    [1]YU Qun, LIU Jiayu. On-line relay protection setting system for mine power grid considering multi-scenario operation mode[J]. Journal of Mine Automation, 2020, 46(12): 38-47. DOI: 10.13272/j.issn.1671-251x.2020100002
    [2]YANG Fan, CHEN Jiang. Present situation and development trend of control and protection technology for mine-used combined switch[J]. Journal of Mine Automation, 2019, 45(8): 79-82. DOI: 10.13272/j.issn.1671-251x.17408
    [3]ZHOU Peiqiang, ZHOU Mengran, XIEYing, WANG Pingping, CAO Zhenguan, LUO Qian. Research of risk assessment reliability of relay protection based on Three-parameter Weibull distributio[J]. Journal of Mine Automation, 2016, 42(8): 56-61. DOI: 10.13272/j.issn.1671251x.2016.08.014
    [4]SONG Hong-wei. Analysis of Setting of Underground High and Low Voltage Protection Value[J]. Journal of Mine Automation, 2012, 38(7): 18-22.
    [5]LIU Feng. Analysis of Processing Method of Protection Re-closure Failures in 220 kV Power Line[J]. Journal of Mine Automation, 2012, 38(4): 85-87.
    [6]WEN Yang-dong, FAN Jun-hua, YU Mao-qua. Application of CPLD in Microcomputer-based Protection Device for Power System[J]. Journal of Mine Automation, 2011, 37(9): 48-51.
    [7]ZHANG Zhao-hua. Current Status of Relay Protection of Mine 35 kV Power Line and Its Improvement Measures[J]. Journal of Mine Automation, 2011, 37(9): 32-34.
    [8]SHI Li-ping, LIANG Jing-wan, LIU Zhi-yua. Design of Calculation Software for Relay Protection Setting of Coal Mine Power Grid[J]. Journal of Mine Automation, 2009, 35(10): 84-87.
    [9]HUANG Jin-hua~, WANG Cheng-yuan~. Research of Current Transformer with High Quality PCB Rogowski Coils Used in Power System of Mining Area[J]. Journal of Mine Automation, 2009, 35(8): 36-40.
    [10]FU Zhou-xing, LI Sheng-jian. Simulation Research in Microprocessor-based Relay Protection Based on Wavelet Transform[J]. Journal of Mine Automation, 2003, 29(4): 6-8.