Analysis of influence factors of polarization spectrum method on state detection of transformer oil-paper insulatio
-
Graphical Abstract
-
Abstract
Application principle of polarization spectrum method based on recovery voltage method was introduced which was used in state detection of transformer oil-paper insulation, and a viewpoint was pointed out that main time constant of polarization spectrum curve was an important factor for judging state of transformer oil-paper insulation. Influence of charging voltage, residual charge and temperature on measurement result of polarization spectrum curve was analyzed separately with conclusions that charging voltage only influenced the maximal value of recovery voltage but did not influence main time constant of polarization spectrum curve, and residual charge and temperature would influence the main time constant. Matters needed attention were proposed that transformer should be fully discharged firstly, charging voltage should be as high as possible in range of 0-2 000 V and environmental temperature should be stable during actual application of polarization spectrum method based on recovery voltage method in state detection of transformer oil-paper insulation.
-
-