矿区35 kV电网线路继电保护的现状及改进措施

Current Status of Relay Protection of Mine 35 kV Power Line and Its Improvement Measures

  • 摘要: 分析了矿区35 kV电网线路继电保护的现状,指出存在的主要问题是保护定值整定、上下时限配合困难,容易引起保护拒动、越级跳闸等故障;提出了采用先进的数字式继电保护装置、采用输电线路纵联保护、增加低电压闭锁保护、加装故障录波装置等线路继电保护改进措施,并通过GPRS分布式故障录波报警系统在矿区电网线路继电保护中的应用实例说明了采用先进的技术装备可提高矿区电网继电保护的可靠性和电网运行的安全稳定性。

     

    Abstract: Current status of relay protection of 35 kV power line of a mine was introduced and main problems were pointed out, namely difficult setting of protection value and matching of up-down time limit which usually lead to faults of protection failure and overstep tripping. Some improvement measures of relay protection were put forward including using advanced digital relay protector, adopting pilot protection of power lines, adding low-voltage latch-up protection, and adding fault recorder. An application example of GPRS distributed alarming system with fault recording in relay protection of mine power line showed that using advanced technique and devices could improve reliability of relay protection of mine power lines and stability of power network running.

     

/