选煤厂煤流系统启停车技术优化

周成军, 张新明, 陶亚东

周成军,张新明,陶亚东.选煤厂煤流系统启停车技术优化[J].工矿自动化,2018,44(1):95-98.. DOI: 10.13272/j.issn.1671-251x.2018.01.2017070036
引用本文: 周成军,张新明,陶亚东.选煤厂煤流系统启停车技术优化[J].工矿自动化,2018,44(1):95-98.. DOI: 10.13272/j.issn.1671-251x.2018.01.2017070036
ZHOU Chengjun, ZHANG Xinming, TAO Yadong. Optimization of starting and stopping technology for coal flow system of coal preparation plant[J]. Journal of Mine Automation, 2018, 44(1): 95-98. DOI: 10.13272/j.issn.1671-251x.2018.01.2017070036
Citation: ZHOU Chengjun, ZHANG Xinming, TAO Yadong. Optimization of starting and stopping technology for coal flow system of coal preparation plant[J]. Journal of Mine Automation, 2018, 44(1): 95-98. DOI: 10.13272/j.issn.1671-251x.2018.01.2017070036

选煤厂煤流系统启停车技术优化

详细信息
  • 中图分类号: TD948/67

Optimization of starting and stopping technology for coal flow system of coal preparation plant

  • 摘要: 针对现有选煤厂煤流系统启停车技术存在启停车时间长、耗电量较大的问题,提出了一种选煤厂煤流系统启停车技术优化方案。以同一台变压器供电的煤流系统设备为启动单元,根据变压器负荷率,同一启动单元内设备同时启动或按设定顺序分批启动,且不同启动单元同时启动;人工测定煤流系统各设备无煤时间节点,在此基础上延后3~5 s作为设备停车时间节点,按顺煤流方向实现各设备无煤即停。实际应用结果表明,采用优化的启停车技术后,启车时间下降了57.9%,停车时间下降了35.2%,取得了良好的节能效果。
    Abstract: For problems of long starting and stopping time and large power consumption existed in current starting and stopping technology for coal flow system of coal preparation plant, an optimization scheme of starting and stopping technology for coal flow system of coal preparation plant was proposed. Equipments of coal flow system powered by the same transformer are taken as starting unit. Equipments in the same starting unit start simultaneously or start in batches in set sequence according to load factor of the transformer, and different starting units start simultaneously. No-coal time node of each equipment of coal flow system is measured manually, and equipment stopping time node delays 3-5 seconds behind the no-coal time node, so as to realize each equipment stopping wihout coal immediately according to direction of coal flow. The actual application results show that starting time reduces 57.9% and stopping time reduces 35.2% by use of the optimization scheme, which achieves good energy-saving effect.
计量
  • 文章访问数:  56
  • HTML全文浏览量:  7
  • PDF下载量:  10
  • 被引次数: 0
出版历程
  • 刊出日期:  2018-01-09

目录

    /

    返回文章
    返回