ZHAO Zeng-yu, MA Gang, WANG Hong-di. Research of Technology of Lightning Protection and Lightning Resistance of High-voltage Lines of Mining Area[J]. Industry and Mine Automation, 2010, 36(9): 138-141.
Citation: ZHAO Zeng-yu, MA Gang, WANG Hong-di. Research of Technology of Lightning Protection and Lightning Resistance of High-voltage Lines of Mining Area[J]. Industry and Mine Automation, 2010, 36(9): 138-141.

Research of Technology of Lightning Protection and Lightning Resistance of High-voltage Lines of Mining Area

  • Publish Date: 2010-09-10
  • The LD-Ⅱ monitoring and positioning system of lightning of mining area was built to analyze thunder density of surface, polarity and amplitude of lightning current, thunder time and position of thunder point in mining area of Yanzhou Mining Group, and distribution of lightning nearby areas of high-voltage lines of mine was researched. A mathematical method was used to make simulation calculation for lightning of three typical towers and lines of the mine grid. Some measures were proposed to improve ability of lightning protection and lightning resistance of the mine grid based on statistical analysis and mathematical calculation, the measures were reducing grounding resistance of towers, using creepage adjustment and adding arrester. The actual application showed that the measures have certain feasibility.

     

  • loading
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (48) PDF downloads(4) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return