DING Wei-min, XU Chun-yu, SONG Jian-cheng. Design of an On-line Detecting System for Dielectric Loss of Mine-used High-voltage Cable[J]. Industry and Mine Automation, 2010, 36(7): 9-12.
Citation: DING Wei-min, XU Chun-yu, SONG Jian-cheng. Design of an On-line Detecting System for Dielectric Loss of Mine-used High-voltage Cable[J]. Industry and Mine Automation, 2010, 36(7): 9-12.

Design of an On-line Detecting System for Dielectric Loss of Mine-used High-voltage Cable

Funds:

"Eleventh Five-Year" National Key Project Support Scheme(2007BAK29B05,2007BAB13B01)

  • In order to solve problems of consuming too much time and resource and unstable precision caused by environment of existing off-line detecting method for dielectric loss of high-voltage cable of coal mine underground,a micro-current sensor was designed for measuring micro grounding current of cable's earth line,and by use of the sensor,an on-line detecting system for dielectric loss of mine-used high-voltage cable was designed based on zero-crossing point comparing method.The composition and on-line detecting principle of the system were introduced.The results of simulation and test showed that the system has stable performance,high measuring precision and strong anti-interference ability,and can on-line measure dielectric loss of high-voltage cable accurately.

     